An independent public resourceEnglish Español

City of Groesbeck

Published drinking-water records and contacts for City of Groesbeck. System TX1470002. Review sources and dates; not a real-time water assessment.

System ID
TX1470002
State or territory
TX
Published population served
4250
System type (source code)
CWS

Published records and dates

Missing records here do not mean the provider did not test. Published records are not a real-time assessment of your tap water.

Published testing results

Selected recent records are shown below. Different sampling locations and dates are not interchangeable. These excerpts are not a complete testing history.

“<” means below the stated reporting limit, not zero. A reported measurement alone is not a safety verdict. Read an example

EPA UCMR 5 — most recent imported sample per substance
SubstancePublished resultReporting limitSample dateSampling location
11Cl-PF3OUdS< 0.005 µg/L0.005 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
4:2 FTS< 0.003 µg/L0.003 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
6:2 FTS< 0.005 µg/L0.005 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
8:2 FTS< 0.005 µg/L0.005 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
9Cl-PF3ONS< 0.002 µg/L0.002 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
ADONA< 0.003 µg/L0.003 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
HFPO-DA< 0.005 µg/L0.005 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
NEtFOSAA< 0.005 µg/L0.005 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
NFDHA< 0.02 µg/L0.02 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
NMeFOSAA< 0.006 µg/L0.006 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
PFBA< 0.005 µg/L0.005 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
PFBS0.0047 µg/L0.003 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
PFDA< 0.003 µg/L0.003 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
PFDoA< 0.003 µg/L0.003 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
PFEESA< 0.003 µg/L0.003 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
PFHpA< 0.003 µg/L0.003 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
PFHpS< 0.003 µg/L0.003 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
PFHxA< 0.003 µg/L0.003 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
PFHxS< 0.003 µg/L0.003 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
PFMBA< 0.003 µg/L0.003 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
PFMPA< 0.004 µg/L0.004 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
PFNA< 0.004 µg/L0.004 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
PFOA< 0.004 µg/L0.004 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
PFOS< 0.004 µg/L0.004 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
PFPeA< 0.003 µg/L0.003 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
PFPeS< 0.004 µg/L0.004 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
PFTA< 0.008 µg/L0.008 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
PFTrDA< 0.007 µg/L0.007 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
PFUnA< 0.002 µg/L0.002 µg/L2024-10-16CITY OF GROESBECK / TRTTAP
lithium< 9 µg/L9 µg/L2024-10-16CITY OF GROESBECK / TRTTAP

Download all EPA UCMR 5 records (CSV)

Lead and copper: 90th-percentile summaries

These describe a monitoring period across sampled locations, not the result at your home. How to read the 90th percentile

Eight most recent imported monitoring summaries
SubstancePublished 90th percentileMonitoring periodSource quarter
Lead (PB90) 0 mg/L2022-01-01 – 2024-12-312026Q3
Lead (PB90) 0.0029 mg/L2021-01-01 – 2021-12-312026Q3
Lead (PB90) 0.0083 mg/L2018-01-01 – 2020-12-312026Q3
Lead (PB90) 0.0034 mg/L2017-07-01 – 2017-12-312026Q3
Lead (PB90) 0.0038 mg/L2017-01-01 – 2017-06-302026Q3
Lead (PB90) 0.01 mg/L2016-01-01 – 2016-12-312026Q3
Lead (PB90) 0.0094 mg/L2015-01-01 – 2015-12-312026Q3
Lead (PB90) 0.005 mg/L2014-01-01 – 2014-12-312026Q3

Published compliance history

29 imported records. Status is as recorded in the source; historical records are not current advisories. Missing records do not establish that no violations occurred.

Twenty most recent imported compliance records
Rule / recordPeriodRecorded statusHealth-based (EPA classification)Source quarter
Consumer Confidence Rule / Consumer Confidence Report Inadequate Reporting2025-07-01 – —ResolvedNo2026Q3
Long Term 2 Enhanced Surface Water Treatment Rule / Monitoring of Treatment (SWTR-Filter)2025-03-01 – 2025-03-31ResolvedNo2026Q3
Long Term 2 Enhanced Surface Water Treatment Rule / Treatment Technique (SWTR and GWR)2025-03-01 – 2025-03-31ResolvedYes2026Q3
Long Term 2 Enhanced Surface Water Treatment Rule / Treatment Technique (SWTR and GWR)2025-02-01 – 2025-02-28ResolvedYes2026Q3
Long Term 2 Enhanced Surface Water Treatment Rule / Monitoring of Treatment (SWTR-Filter)2025-02-01 – 2025-02-28ResolvedNo2026Q3
Stage 2 Disinfectants and Disinfection Byproducts Rule / Maximum Contaminant Level Violation, Average2021-01-01 – 2021-03-31ResolvedYes2026Q3
Stage 2 Disinfectants and Disinfection Byproducts Rule / Maximum Contaminant Level Violation, Average2020-10-01 – 2020-12-31ResolvedYes2026Q3
Stage 2 Disinfectants and Disinfection Byproducts Rule / Maximum Contaminant Level Violation, Average2020-07-01 – 2020-09-30ResolvedYes2026Q3
Stage 2 Disinfectants and Disinfection Byproducts Rule / Maximum Contaminant Level Violation, Average2019-04-01 – 2019-06-30ResolvedYes2026Q3
Public Notice Rule and Revised PN Rule / Public Notification Violation for NPDWR Violation2018-12-31 – —ResolvedNo2026Q3
Long Term 2 Enhanced Surface Water Treatment Rule / Failure to Filter (SWTR)2018-12-01 – —ResolvedYes2026Q3
Long Term 2 Enhanced Surface Water Treatment Rule / Failure to Filter (SWTR)2018-11-01 – —ResolvedYes2026Q3
Long Term 2 Enhanced Surface Water Treatment Rule / Failure to Filter (SWTR)2018-03-01 – —ResolvedYes2026Q3
Public Notice Rule and Revised PN Rule / Public Notification Violation for NPDWR Violation2017-07-31 – —ResolvedNo2026Q3
Public Notice Rule and Revised PN Rule / Public Notification Violation for NPDWR Violation2017-07-01 – —ResolvedNo2026Q3
Public Notice Rule and Revised PN Rule / Public Notification Violation for NPDWR Violation2017-06-12 – —ResolvedNo2026Q3
Public Notice Rule and Revised PN Rule / Public Notification Violation for NPDWR Violation2017-06-12 – —ResolvedNo2026Q3
Long Term 2 Enhanced Surface Water Treatment Rule / Failure to Filter (SWTR)2017-06-01 – —ResolvedYes2026Q3
Long Term 2 Enhanced Surface Water Treatment Rule / Failure to Filter (SWTR)2017-05-01 – —ResolvedYes2026Q3
Long Term 2 Enhanced Surface Water Treatment Rule / Failure to Filter (SWTR)2017-04-01 – —ResolvedYes2026Q3

Source dates and refresh checks

A refresh check is not a sample date. Publication periods, sample dates and checks are shown separately.

Administrative contact (EPA filing)

Odocharty, Ray: 254-729-3293

An administrative filing contact may not be a customer-service line. Confirm current contact details with the provider.